HUBBLE SPACE TELESCOPE - Continuing to collect World Class
Science
DAILY REPORT #4861
PERIOD COVERED: 5am June 5 - 5am June 8, 2009 (DOY
156/0900z-159/0900z)
OBSERVATIONS SCHEDULED
COS/NUV 11467
NUV Detector Internal Functionality and Operation
The functionality and operation of the COS NUV detector
will be tested
using internal sources. Several science exposures will be
taken in
TIME-TAG using both the DEUTERIUM and Pt/Ne lamps. This is
SMOV Activity
COS-06
COS05/NUV 11466
NUV Detector Dark
Measure the NUV detector dark rate by taking long science
exposures with
no light on the detector. The detector dark rate and
spatial
distribution of counts will be compared to pre-launch data
in order to
verify the nominal operation of the detector, and for use
in the CalCOS
calibration pipeline. Variations of count rate as a
function of orbital
position will be analyzed to find dependence of dark rate
on proximity
to the SAA.
FGS/S/C 11458
Optimizing FGS2R2 Performance with the AMA
This proposal satisfies SMOV4 AD OTA/FGSS-054. S-curves
with PUPIL and
F583W will be obtained at selected locations within the
FGS2R2 FOV
during SMOV4. These data will be will be used to adjust
the AMA so as to
align the HST pupil onto the interferometer's Koesters
prisms. The final
AMA position will be set to produce an acceptable set of
S-curves across
the FGS2R2 FOV. The AMA will be adjusted using
CCL/instructions from the
ground. It is intended that this proposal executes during
the SMOV4 BEA
and will require several (on the order of 4) iterations to
achieve
optimal interferometric performance.
STIS07/CCD 11404
CCD Dark and Bias Monitor for SMOV4/Cycle 17 Activity
STIS-07
Monitor the darks for the STIS CCD. Monitor the bias in
the 1x1, 1x2,
2x1, and 2x2 bin settings at gain=1, and 1x1 at gain = 4,
to build up
high-S/N superbiases and track the evolution of hot
columns.
STIS13/CCD 11388
STIS-13 CCD Spectroscopic Image Quality and ACQ Tests
Check image quality along the 52x0.1 slit in combination
with the G230LB
grating. The target star will be positioned at several
positions along
the slit including 52X0.1 (nominal center position),
52X0.1E1 (CTE
position) and 51X0.1D1 (MAMA acquisitions near low
background for FUV
MAMA). Positioning of the target will be done utilizing
PATTERN and
offsets of 0.1 arcseconds between five positions.
Sufficient targets
will be selected, and contingency visits prepared, to
allow this
activity to occur any time during the BEA period.
ACS/SBC 11372
SBC UV Contamination Check
ACS/SBC throughput in the far-UV will be monitored during
the bright
earth avoidance period through use of two non-BEA visits,
each of one
orbit separated by one week allowing observations of NGC
6681. A waiver
for two non-BEA orbits during BEA was previously granted.
Exposures will
be taken in PR110L, F115LP, F125LP, F140LP, F150LP and
F165LP as in
recent UV Monitor program observations. These results will
be one of the
activities determining if the BEA can be ended. A third
visit just after
BEA ends will repeat the above monitoring and include one
orbit with
F122M. ON HOLD visits 4 and 5 would substitute for 1 and 2
if SM4 is
delayed.
COS23/S/C/FUV 11356
COS FUV Initial On-Orbit Turn-On
This proposal specifies the procedure for SMOV initial HV
turn-on and
ramp-up of the COS FUV detector. (The FUV will have been
commanded to
its Operate state to support execution of proposal 11353.)
The procedure
is detailed in the Observing Description, but in summary,
the following
is done: The initial transition from FUV Operate to HVLow
is broken into
two parts, with a gap of 4 hours between turning on the HV
and ramping
to the HVLow (SAA) voltage. This will be followed by 5
cycles of HV
ramp-up and return to HVLow. Cycles will ramp up to
successively higher
(magnitude) voltage, with the fifth cycle going to the
nominal operating
values. There will be a gap of at least 4 hours between
cycles. All HV
ramp-up will be done at 10 sec per HV "step".
The step rate and cycle
voltage values (for Segments A and B) must be patched in
FSW in each
cycle prior to the HV ramp commanding. Memory monitors
will be set on
the patched memory locations. Immediately after any HV
commanding, and 4
hours after ramp-up commanding, the DCE memory will be
dumped.
Immediately after HV ramp-up commanding higher than HVLow,
short DARK &
WAVE exposures will be obtained. Visits 01 and 02, and all
the
subsequent even numbered visits (the ones 4 hours after HV
ramp-ups),
end with NSSC-1 COS event flag 3 being set. If the flag
remains set,
subsequent FUV commanding will be skipped. Thus,
Operations Requests
must be in place to clear the flag prior to those
subsequent visits.
Real-time monitoring of the telemetry will be used to
guide the
decisions whether or not to clear the flag. The final
visit (13)
provides a scheduled final opportunity to clear flag 3,
and if the flag
is cleared, initiates nominal FUV HV commanding and
requests a DARK
exposure.
STIS17/MA/S/C 11350
FUV MAMA HV Recovery
This proposal addresses the concerns over Cesium migration
from the
FUV-MAMA photocathode into the pores of the microchannel
plate and lays
out the procedures necessary to permit a safe and
controlled recovery of
the FUV-MAMA detector to science. This procedure should
only be used
during the SMOV4 high voltage recommissioning phase for
the FUV-MAMA.
After that, the normal ramping procedure should be used.
This proposal
is loosely based on proposal 10036, STIS MAMA Anomalous
Recovery, with
the differences summarized below: (1) additional plateaus
during voltage
commanding, (2) longer dwells after each 50 V step, (3)
intermediate
ramp re-structured into 2 parts, (4) change in yellow and
red limits and
the MCP Hi limit, setting new values for the next plateau,
and (5)
adding a fold test at 300V below the nominal MCP voltage.
The recovery
consists of four separate and unique procedures (visits)
and they must
be completed successfully and in order. They are: (1) a
signal
processing electronics check, (2) 1st high voltage ramp-up
to an
intermediate MCP voltage of -1500 V with limits
modifications and
voltage plateaus, (3) 2nd high voltage ramp-up to an
intermediate MCP
voltage of -1950 V (300 V below the nominal MCP voltage)
with limits
modifications and voltage plateaus followed by a fold distribution
test,
and (4) the final high voltage ramp-up to the full
operating voltage,
again with limits modifications and voltage plateaus,
followed by a fold
distribution test. During the 1st high voltage ramp-up,
diagnostics are
performed followed by a dark exposure. During the 2nd and
3rd high
voltage ramp-ups, diagnostics are performed followed by a
dark, flat
field ACCUMs, and a fold analysis test. All required
parameters are
defined in 07-248 FUV and NUV SMOV Ramp-up Parameters
Excel workbook.
Supports Activity STIS-17
FLIGHT OPERATIONS SUMMARY:
Significant Spacecraft Anomalies: (The following are
preliminary reports
of potential non-nominal performance that will be
investigated.)
HSTARS:
11867 - At 157/13:04:22z GSAcq (1,3,3) scheduled from
13:00:29z -
13:07:30z resulted in Fine Lock Back-up (1,0,1).
Observations affected: None
11869 - GSAcq(1,3,3) scheduled at 156/23:23:33z - 23:31:04
resulted in
fine lock backup (3,0,3) using FGS-3 due to Scan Step Limit Exceeded on
FGS-1.
Observations possibly affected: COS 8 - 12 Proposal ID#11467 and
Astrometry Proposal ID#11458
COMPLETED OPS REQUEST:
18474-0 - 2nd AMA Move for FGS2R2 @ 156/0951z
18490-0 - Clear COS Event Flag 3 after FUV initial turn on
Part 1 completes @ 156/1330z
18493-0 - Uplink OBSINT Gyro Bias Update @ 156/1542z
18496-1 - Perform COS Time code update @ 157/1413z
18495-0 - Clear COS Event Flag 3 after FUV initial turn on
Part 2 completes @ 157/1426z
18468-0 - Clear STIS Event Flag 2 (MAMA1 Checkout Part 4)
@ 157/1448z
18497-0 - 3rd AMA Move for FGS2R2 @ 158/2239z
COMPLETED OPS NOTES: (None)
SCHEDULED
SUCCESSFUL
FGS GSAcq
25
25
FGS
REAcq
1
1
OBAD with Maneuver
18
18
SIGNIFICANT EVENTS:
Flash Reports:
-The 2nd FGS2R2 AMA Move was executed at 156/09:39-09:52z.
-The COS FUV HV was ramped to HVlow (-4069 volts) on both
segments A and B at 156/16:55z
-At 157/20:54z the COS FUV HV was partially ramped to
HVNom (-4916/-4869 volts) on both
segments A and B respectively.
-The 3rd FGS2R2 AMA Move was executed at 158/22:30-22:39z